CJ2M, USB
Setup I/O Table,
-online PLC
Click I/O Table (program mode)
Create Register I/O Table
Intialize CPU Bus setting? OK
Check
Done.
Clear Error.
PLC (program mode)-Clear all Memaory,-clear error log-utilize-OFF/ON
Hardware seeting, DIP SWITCH 1=on=mA, 0ff=V
Clik Memory
D for Data
m=20000, right click, binnary
m0=0200 (input 1, 0050, input 3, 0010 (input 1-V)
m1=0010, (mA) 0000 (V)
m2=0002
m6=0001, =input 1, 0001=no mean value, (baca mean lebih tepat)
m18=0000 (Range, 1ms=4k, 250ms=8k)
m27=0000 (scale function)input 1
m28=0FA0 (Range)
m35=0010 (mA) 0000 (V)
0000 1111 1010 0000
0 F A 0
Ringh click, online, Transfer to PLC, compare, monitor, save, off, on.
Note:
I/P 1=2009.04
I/P 2=2009.05
I/P 3=2009.06
I/P 4=2009.07
MOV 2005=i/p 1
MOV 2006=i/p 2
MOV 2007=i/p 3
MOV 2008=i/p 4
Contoh I/P3 Voltage
m0=0040
m1=2000
m2=000?
m8=0001
m18=0000
m31=0000
m32=0FA0 (Range)
m35=0050 (mA)
Projek level pump |
projek analog imput GL and LT 12mA |
M0=pilih input dan output
ReplyDelete0,1,=Output
4,5,6,7,=Input
M1=Range
0-3, output
8-15, input
(01) Volt, (10)mA
M6 hingga M0, Input no mean value, 0001
M18, 4000 decimal or 8000?
M19-22, scaling output
M27 hingga M34 Range scaling,
0
3E8
7D0
BB8
FA0
M35, pilih V or I?